HST calculation of a 10 kV oil‐immersed transformer with 3D coupled‐field method
Jiangjun Ruan, Yongqing Deng, Daochun Huang, Cihan Duan, Ruohan Gong, Yu Quan, Yuanchao Hu, Qingyu Rong
Wuhan University of Technology Wuhan University Wuhan University of Science and Technology Shandong University of Technology
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
Transformer winding hot‐spot temperature (HST) is one of the important factors affecting transformer oil–paper insulation deterioration. This study presents a three‐dimensional coupled electromagnetic‐fluid‐thermal analysis method for HST calculation in a 10 kV oil‐immersed distribution transformer, the influence of the transformer internal metal structure parts on the HST of the winding is considered in the simulation. Combining electromagnetic‐field calculation with no‐load test and load test of the transformer provides a more accurate method to determine internal losses of the transformer. Taking those power losses as heat sources, the transformer fluid‐thermal field analysis is conducted with the finite volume method. The variation of physical parameters of transformer oil with temperature is considered in the simulation. On the basis of the equivalent thermal resistance theory, the equivalent thermal conductivities of transformer windings are obtained. The simulation results deduced from the proposed method agree well with the experimental ones, which are obtained with fibre optic temperature sensors during the transformer temperature rise test, the maximum temperature difference is <3°C. The results validated the validity and accuracy of the proposed transformer HST calculation method.
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
工程Power Transformer Diagnostics and Insulation
High voltage insulation and dielectric phenomena · Thermal Analysis in Power Transmission
参考文献 29
此处列出前 3 条
引用本文 52
按被引量排序,此处列出前 3 条