Modeling of Wastewater Treatment and Dynamic Optimization Control of Dissolved Oxygen Concentration in Aeration Tanks
Wanjie Ding, Liu Zhao, Xiaohong Wang
University of Jinan
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
The wastewater biochemical treatment process exhibits significant nonlinearity, posing challenges for the design and optimization of control strategies. To address these challenges, Benchmark Simulation Model No. 1 for activated sludge wastewater treatment was first developed using MATLAB’s S-function and the Simulink platform. Comprehensive open-loop simulations were conducted using both constant and dynamic influent data under different weather conditions (clear, rainy, and stormy). Compared to actual reference data, the simulations yielded a mean absolute error of only 0.051152 g/m3 in the effluent TSS concentration of the top layer of the secondary clarifier, verifying the accuracy and effectiveness of the model. Second, PI control experiments on dissolved oxygen concentration revealed that, under stormy conditions, the total nitrogen content in the wastewater failed to meet regulatory standards. Nonlinear model predictive control was applied to address this, and random excitation was introduced into the model’s open-loop simulations to enhance prediction accuracy. The resulting data were used to optimize and train various machine learning models, including backpropagation (BP) neural networks, random forests, support vector machines, and least squares support vector machines (LSSVMs), using the particle swarm optimization (PSO) algorithm. Third, the PSO-LSSVM prediction model, which demonstrated the highest prediction accuracy, was selected and combined with the fruit fly optimization algorithm to determine the optimal control parameters for model predictive control. Simulation results confirmed that all performance indicators met the standards under all tested weather conditions. Finally, traditional constant dissolved oxygen control strategies have been shown to result in energy waste. By dynamically adjusting the dissolved oxygen set point, aeration energy consumption was reduced by 3.27% without significantly affecting effluent water quality.
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
物理Wastewater Treatment and Nitrogen Removal
Advanced Control Systems Optimization · Water Quality Monitoring and Analysis
参考文献 38
此处列出前 3 条
引用本文 3
按被引量排序,此处列出前 3 条