Performance of throttle-cycle coolers operating with mixed refrigerants designed for industrial applications in a temperature range 110 to 190 K
O. Podtcherniaev
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
The efficiency of coolers designed to provide refrigeration for industrial equipment is discussed. Experience accumulated during more than twenty years of manufacturing shows that multistage auto-cascade coolers provide high refrigeration performance along with rapid cool down and defrost. Both single-stage and two-stage throttle cycles have been analyzed. Comparative data on the performance of the cycles are obtained with a computer model that includes an equation of state to calculate thermodynamic properties of mixed refrigerants. Both flammable argon-hydrocarbon- and nonflammable argon-hydrofluorocarbon-based mixed refrigerants have been considered. Non-flammable environmentally friendly mixed refrigerants include commercially available components. The experimental data were obtained for coolers based on a single-stage compressor. The tested systems provided refrigeration capacity from 500 to 3600 W depending on the compressor displacement volume. A Carnot efficiency coefficient as high as 0.21 was achieved. This corresponds to the efficiency of conventional freezers operating at temperatures above 230 K.
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
工程Refrigeration and Air Conditioning Technologies
Advanced Thermodynamic Systems and Engines · Thermodynamic and Exergetic Analyses of Power and Cooling Systems
参考文献 5
此处列出前 3 条
引用本文 21
按被引量排序,此处列出前 3 条