Advanced partial discharge diagnostic of MV power cable system using oscillating wave test system
Ε. Gulski, F.J. Wester, Johan J. Smit, P.N. Seitz, M. Turner
Delft University of Technology
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
To obtain a sensitive picture of discharging faults in power cables the PD should be ignited, detected, and located at power frequencies that are comparable to operating conditions at 50 or 60 Hz. In this way, realistic magnitudes in [pC] and reproducible patterns of discharges in a power cable can be obtained. PD measurements during service as well as on-site continuous energizing at 50 (60) Hz of MV cables are not always economically realistic for on-site inspections. Different energizing methods have been introduced and employed during recent years. Therefore, based on the assumption that sensitive detection of critical PD sites occurs by a method mostly similar to 50 Hz energizing conditions, a method as introduced for on-site PD diagnosis of MV cables is discussed: oscillating wave test system (OWTS).
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
材料 / 化学High voltage insulation and dielectric phenomena
Electrical Fault Detection and Protection · Power Transformer Diagnostics and Insulation
参考文献 7
此处列出前 3 条
引用本文 90
按被引量排序,此处列出前 3 条