Mobile Battery Energy Storage Systems for Onshore Drilling Electrification
Tanis Reed, Jorge Valdez, Marcel Snijder, Nate Norris
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
A growing trend in the industry is to supply more drilling loads with electrical power from the grid, rather than from onsite generators. Mobile substations connected to operator-owned utility lines can power these drilling loads if there is enough capacity in the system, but for many development areas, it is difficult to justify this extra capacity. Mobile Battery Energy Storage Systems can be deployed and connected to mobile substations to solve this problem. Due to the unique load profile of drilling operations, which can have an average load of less than 1.5-2 MW and usually reach peak demand for a short period, BESS’s (Battery Energy Storage Systems) can quickly discharge to meet load requirements during periods of peak demand, then recharge during normal operation, thus lowering the peak demand seen by the system and allowing for greater reach of electrified drilling operations. This paper presents a case study of the use of such a system, and addresses issues with power system planning, mobile system architecture, contingency operations such as high-speed load shedding and load-limiting controls, islanding and parallel operations and protection, as well as optimization techniques for backup diesel generators whether islanded or paralleled to the grid.
逐年被引趋势
暂无年度引用数据
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
工程Power Systems and Renewable Energy
Microgrid Control and Optimization · Smart Grid Energy Management