Research on High-Frequency Current and Electromagnetic Radiation Characteristics During the Switching Process of Tap Changer
Ninghui He, Xiu Zhou, Bo Liu, Pei Zhang, Wenchang Ma
State Grid Corporation of China (China)
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
During the switching process of vacuum on-load tap changer, high frequency oscillation current is generated in the circuit due to the opening and closing of contacts, and the electromagnetic wave generated can be used to diagnose the status of tap changer. In order to understand the mechanism of high-frequency current and electromagnetic radiation in the process of tap changer switching, the equivalent circuit model of contact opening and closing is firstly established in this paper, and the corresponding relationship between circuit capacitance and inductance parameters and contact size and circuit lead length is analyzed; Then a simulation test platform for tap changer switching is built. The influence of contact opening and closing speed and opening and closing phase on high-frequency current and electromagnetic radiation characteristics cannot be studied experimentally. A method for monitoring arcing time based on electromagnetic radiation is proposed. The research conclusion is of great significance to the state evaluation method of vacuum on-load tap changer.
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
工程Electromagnetic Compatibility and Noise Suppression
Vacuum and Plasma Arcs · Electrical Contact Performance and Analysis
参考文献 4
此处列出前 3 条
引用本文 1
按被引量排序,此处列出前 3 条