Dimensioning of Sheath Voltage Limiters for Single- Core Power Cables Connecting an Overhead Transmission Line to a 150 kV Substation
Alexandros Y. Hadjicostas, Zacharias G. Datsios, Pantelis N. Mikropoulos, Thomas E. Tsovilis, Argiris Kagiannas, Z. Politis, Georgios D. Peppas
Aristotle University of Thessaloniki Technical University of Crete
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
This case study evaluates the stresses of sheath voltage limiters installed at the open end of single-point bonding systems employed for two single-core power cable circuits (lengths: 120 m and 50 m). These cable circuits connect one circuit of a 150 kV double-circuit overhead transmission line to a 150/33 kV substation. Detailed simulations are performed using the ATP-EMTP software for four main scenarios: (i) steady-state operating conditions, (ii) single-phase and three-phase short circuits, (iii) lightning strikes to towers, and (iv) shielding failures at the incoming 150 kV overhead line. For the lightning-related scenarios (iii and iv), the residual voltage and the surge current through the sheath voltage limiters are computed, considering the effects of the instantaneous value of the AC operating voltage, the time to half value, and the amplitude of the lightning return- stroke current. Stress on the sheath voltage limiters is analyzed in terms of charge transfer and specific energy obtained through simulations. Finally, the minimum required characteristics of the sheath voltage limiters are determined and discussed in the context of appropriate dimensioning in engineering applications.
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
工程Thermal Analysis in Power Transmission
High voltage insulation and dielectric phenomena · Electromagnetic Compatibility and Noise Suppression
参考文献 36
此处列出前 3 条
引用本文 3
按被引量排序,此处列出前 3 条