Arc Fault Detection Method Based on CZT Low-Frequency Harmonic Current Analysis
Giovanni Artale, Antonio Cataliotti, Valentina Cosentino, Dario Di Cara, Salvatore Nuccio, Giovanni Tinè
University of Palermo National Research Council
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
This paper presents a method for the detection of series arc faults in electrical circuits, which has been developed starting from an experimental characterization of the arc fault phenomenon and an arcing current study in several test conditions. Starting from this, the authors have found that is it possible to suitably detect arc faults by means of a high-resolution low-frequency harmonic analysis of current signal, based on chirp zeta transform, and a proper set of indicators. The proposed method effectiveness is shown by means of experimental tests, which were carried in both arcing and nonarcing conditions and in the presence of different loads, chosen according to the UL 1699 standard requirements.
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
工程Electrical Fault Detection and Protection
Power Quality and Harmonics · Electrical Contact Performance and Analysis
参考文献 27
此处列出前 3 条
引用本文 185
按被引量排序,此处列出前 3 条