Cross-Forming Control and Fault Current Limiting for Grid-Forming Inverters
Xiuqiang He, Maitraya Avadhut Desai, Linbin Huang, Florian Dörfler
ETH Zurich Automatic Control Laboratory
阅读操作
确认中在文库中上传 PDF 后可生成中文音频讲解。
摘要与影响
This article proposes a “cross-forming” control concept for grid-forming inverters operating against grid faults. Cross-forming refers tovoltage angle formingandcurrent magnitude forming. It differs from classical grid-forming and grid-following paradigms that feature voltage magnitude-and-angle forming and voltage magnitude-and-angle following (or current magnitude-and-angle forming), respectively. The cross-forming concept addresses the need for inverters to remain grid-forming (particularlyvoltage angle forming, as required by grid codes) while managingfault current limitation. Simple and feasible cross-forming control implementations are proposed, enabling inverters to quickly limit fault currents to a prescribed level while preserving voltage angle forming for grid-forming synchronization and providing dynamic ancillary services, during symmetrical or asymmetrical fault ride-through. Moreover, the cross-forming control yields an equivalent system featuring aconstantvirtual impedance and a “normal form” representation, allowing for the extension of previously established transient stability results to include scenarios involving current saturation. Simulations and experiments validate the efficacy of the proposed cross-forming control implementations.
逐年被引趋势
关键指标
同类平均 = 1
同领域 · 同年份 · 同类型
Google Scholar 与 OpenAlex 的被引统计范围不同,数值存在差异属正常。
AI 辅助阅读
依据:摘要
可就本文提问;依据不足时会说明。
学术脉络
学科主题
工程HVDC Systems and Fault Protection
High-Voltage Power Transmission Systems · Islanding Detection in Power Systems
参考文献 75
此处列出前 3 条
引用本文 57
按被引量排序,此处列出前 3 条