In the event of asymmetric grid faults, virtual synchronous generators may suffer from severe overcurrent, transient instability, and degraded power quality. To address these issues, this article proposes an asymmetric fault ride-through control method based on direct reconstruction of the internal voltage reference after grid faults. In the proposed method, the reactive power loop is frozen, while the active power loop is retained. For different grid-voltage sag depths, the internal voltage reference is rapidly reconstructed by comprehensively considering current limiting, three-phase current symmetry, positive-sequence voltage support, and converter capacity. To enhance transient stability, the active power reference is adaptively adjusted to drive the power angle toward its target value, while accounting for the active power generated by negative-sequence components and the variation in voltage amplitude. Hardware-in-the-loop experimental tests show that the proposed strategy can suppress fault overcurrent, maintain three-phase current symmetry, and improve transient stability during asymmetric grid faults.